Cooling Tower: Relative Plan Area (RPA) and Relative Power Consumption (RPC) with respect to Relative Cooling Capacity (RCC)

The following graph illustrates the relationship between the Relative Plan Area (RPA) and Relative Power Consumption (RPC) with respect to increasing Relative Cooling Capacity (RCC), and describes how to double the relative cooling capacity with the same values of all other thermal and size conditions.
RCC
RPA
RPC
1
1.00
1.00
1.1
1.15
1.33
1.2
1.31
1.73
1.3
1.48
2.20
1.4
1.66
2.74
1.5
1.84
3.38
1.6
2.02
4.10
1.7
2.22
4.91
1.8
2.41
5.83
1.9
2.62
6.86
2
2.83
8.00




In order to double the capacity (Relative Cooling Capacity) with the same values of all
other thermal and size conditions, the following must be done:
  • Increase the surface of the tower by 2 ^ 1.5 times, that is, 2 (double) to the power of 1.5 = 2.83. 
     The tower must be 2.83 times bigger with the same fan, air flow capacity, etc. 
     
      OR:
  • Increase the power to 2 ^ 3 times, that is, 2 (double) to the power of 3 = 8. 

         The power of the engine must be 8 times greater with the same surface of the tower

          (verifying the speeds etc.)

References:
Comparative Evaluation of Different Packings 
Péter Gosi, Institute far Electric Power Research (VEIKI), Budapest, Hungary

Judith Halasz, Universidade Estadual de Campinas, Sao Paulo, Brazil,

Pal Kostka

4 Thoughts to “Cooling Tower: Relative Plan Area (RPA) and Relative Power Consumption (RPC) with respect to Relative Cooling Capacity (RCC)”

  1. Atul Joshi

    It is truly a very valuable information Bruno.

  2. Thanks Atul, all my posts are a collection of over 50 years of my experiences as a designer and manufacturer with cooling towers. Thanks again and keep following me.

  3. Howdy very cool web site!! Man .. Beautiful .. Superb ..
    I’ll bookmark your website and take the feeds also? I’m happy to find so many useful information right here in the publish, we’d like work
    out more strategies on this regard, thanks for sharing.
    . . . . .

    1. TURBOsplash PAC NERIFILL

      Grazie per il tuo apprezzamento. Sicuramente condividere le esperienze che abbiamo acquisito è sempre costruttivo. la mia email: [email protected]

Leave a Comment